Hall Sensors

VS3-100/1500A Hall Voltage Sensor

NAME:VS3-100 1500A Hall Voltage Sensor
  • ELECTRICAL  DATA

Nominal voltage 1500 V
Measuring range 0…±2250 V
Turns ratio 10000:2000  
Measuring resistance Rm  150(max) Ω
Supply voltage ±15±5% V
Output current 50 mA
Accuracy at +25℃ 0.5 %
Isolation voltage 10KV RMS/50Hz/1min KV

 

  • ACCURACY  DYNAMIC  PERFORMANCE

Current consumption 10+IM mA
Offset current(Ta =+25℃) ±0.3 mA
Temperature drift(-25℃…+70℃) <±0.3~±0.5 mA
Linearity ≤0.1 %FS
Response time 40…200 μS
Frequency bandwidth 0…20 KHz

  • GENERAL  DATA

Secondary resistance 60 Ω
Primary resistance 1.8K+R1 Ω
Operating temperature -25~+70
Storage temperature -25~+85

  • Dimensions(mm)