Hall Current Sensors

Hall Current Sensor

NAME:K4 Serial Hall Current Sensor
  • Specifications

Nominal current 300 500 1000 1500 2000 A
Measuring range 600 1000 2000 3000 4000 A
Nominal analogue output  current Voltage 4±1% V
Supply voltage ±15(±5%) V
Zero offset voltage at +25℃ 10 mV
Offset Voltage Temperature Characteristic ≤±1 mV/℃
Linearity ≤1 %FS
Response Time ≤7 μS
Galvanic isolation 50HZ,1min,2.5 KV
Operating temperature -40~+85
Storage temperature -55~+125

 

  • Dimensions(mm)

  • Note
  • 1. The current will be measured at the output pin when it gets across the sensor. (Wrong connection may damage the sensor).
  • 2. The sensor with different output or input current can be made according to your requirements