NAME:D8-1000A Hall Current Sensor
  • ELECTRICAL  DATA

Nominal current 1000 A
Measuring range 2000 A
Turns ratio 1:5000  
Measuring resistance with±15V @±1000Amax  30(max) Ω
@±1200Amax  20(max) Ω
with±24V @±1000Amax  75(max) Ω
@±2000Amax  15(max) Ω
Supply voltage ±15~ ±24 V
Nominal analogue output current 200±0.5% mA
Accuracy at +25℃ 0.1 %
Galvanic isolation 50HZ,1min,6 KV

 

  • ACCURACY  DYNAMIC  PERFORMANCE

Zero offset current ±0.1 mA
Thermal drift of  offset current -10~+85℃,±0.4 mA
Response time <1 µs
Linearity ≤0.1 %FS
Bandwidth(-3dB) DC…150 KHz
di/dt >100 A/μs

 

  • GENERAL  DATA

Secondary internal resistance 46 Ω
Operating temperature -10~+85
Storage temperature -25~+100

 

  • Dimensions(mm)

  • Operating instructions
  • 1.It is positive when Ip flows in the direction of the arrow.
  • 2.Temperature of the primary conductor should not exceed 100 ℃。
  • 3.Dynamic performances (di/dt and the response time) are best with a single bar completely filling the primary hole.
  • 4.In order to achieve the best magnetic coupling,the primary windings have to be wound over the top edge of the device