Hall Current Sensor

Hall Current Sensor

NAME:D6-500A Hall Current Sensor
  • ELECTRICAL  DATA
    Nominal current 500 A
    Measuring range 800 A
    Turns ratio 1:5000  
    Measuring resistance with±15V  @±500Amax  40(max) Ω
    @±800Amax   5(max) Ω
    with±18V  @±500Amax  60(max) Ω
    @±800Amax  15(max) Ω
    Supply voltage ±15±5% V
    Nominal analogue output current 100±0.5% mA
    Accuracy at +25℃ 0.1 %
    Galvanic isolation 50HZ,1min,6 KV


 

  • ACCURACY  DYNAMIC  PERFORMANCE

Zero offset current ±0.1 mA
Thermal drift of  offset current -40℃~+70℃,±0.4 mA
Response time <1 µs
Linearity ≤0.1 %FS
Bandwidth(-3dB) DC…100 KHz
di/dt >100 A/μs

 

  • GENERAL  DATA

Secondary internal resistance 70 Ω
Operating temperature -40~+70
Storage temperature -40~+85

 

  • Dimensions(mm)

  • Operating instructions
  • 1.It is positive when Ip flows in the direction of the arrow.
  • 2.Temperature of the primary conductor should not exceed 100 ℃。
  • 3.Dynamic performances (di/dt and the response time) are best with a single bar completely filling the primary hole.
  • 4.In order to achieve the best magnetic coupling,the primary windings have to be wound over the top edge of the device.